YSLC11Y-..Z
PUR Control Cables
Construction
A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2 with enhanced properties
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable) extruded dummy element or flexible rope
C Cabling conductors cabled in concentric layers
D Taping polyester foil
E Screen tinned copper braid, coverage approx. 82%
F Jacket polyurethane, shiny finish
F Colour grey RAL 7001
YSLC11Y-..Z
![YSLC11Y-..Z [GCE Cables - Italy]](/images/stories/cables/Control_and_Power_Cables/YSLC11Y-..Z.jpg)
Technical Data
Conductor resistance R 0,50 mm2 < 39,0 Ohm/km
0,75 mm2 < 26,0 Ohm/km
1,00 mm2 < 19,5 Ohm/km
1,50 mm2 < 13,3 Ohm/km
2,50 mm2 < 7,98 Ohm/km
4,00 mm2 < 4,95 Ohm/km
6,00 mm2 < 3,30 Ohm/km
10,00 mm2 < 1,91 Ohm/km
16,00 mm2 < 1,21 Ohm/km
25,00 mm2 < 0,780 Ohm/km
35,00 mm2 < 0,554 Ohm/km
50,00 mm2 < 0,386 Ohm/km
Insulation resistance RI > 20 MOhm x km
Transfer impedance ZT < 250 mOhm/m
Nominal voltage U0/U 300/500 V
Test voltage UT 3000 V
Bending radius r min.
mobile application 15 x cable diameter
fixed installation 4 x cable diameter
Temperature range
mobile application - 5 °C up to + 80 °C
fixed installation - 40 °C up to + 80 °C
Oil resistance HD 505.2.1, VDE 0472 part 803 class A/B
Hydrolysis resistance HD 22.10
Ozone resistance HD 22.2
Options
- UL/CSA versions
300 V 80 °C (slimline)
for cross sections up to 1,50 mm2
600 V 80 °C (larger diameters)
for the whole range - low adhesion jacket with matte finish
- additional polyester fleece taping over
the screen - flame retardant as per IEC 60332-1
- FRNC version in compliance with
IEC 60332-1 and IEC 60754-1 & -2
type TPESLC11Y-..Z FRNC - other core configurations, cross
sections and jacket colours
manufactured upon request