PUR Power Cables

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation EPR compound type EI6
B Identification colour coded as per HD 308 S2
C Central filler (where applicable) extruded dummy element
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Jacket polyurethane, shiny finish
E Colour orange RAL 2003

H07BQ-F

Technical Data

Conductor resistance                    R                 1,50 mm2 < 13,30   Ohm/km
                                                                      2,50 mm2 <   7,98   Ohm/km
                                                                      4,00 mm2 <   4,95   Ohm/km
                                                                      6,00 mm2 <   3,30   Ohm/km
                                                                    10,00 mm2 <   1,91   Ohm/km
                                                                    16,00 mm2 <   1,21   Ohm/km
Insulation resistance                     RI              > 20 MOhm x km
Nominal voltage                            U0/U          450/750 V
Operating voltage                          UB0/UB     495/825 V AC
                                                                    743/1238 V DC
Test voltage                                  UT             2500 V

Bending radius                              r min.
       mobile application                                   5 x cable diameter
       fixed installation                                      3 x cable diameter

Max. admissible conductor temperature
       continuous                                             +   90 °C
       in case of short circuit                             + 200 °C

Temperature range
       mobile application                  - 30 °C up to + 80 °C
       fixed installation                     - 40 °C up to + 90 °C

Resistance to low                         HD 505.1.4
       temperatures
Oil resistance                               HD 505.2.1, VDE 0472 part 803 class A/B
Hydrolysis resistance                    HD 22.10
Ozone resistance                          HD 22.2
Halogen content                            IEC 60754-1, EN 50267-2-1
Corrosivity                                    IEC 60754-2, EN 50267-2-2

Notes

  • S07BQ-F does not carry the HAR
    mark
  • the construction without an extruded
    barrier layer makes these cables ideal
    for spiralling

Options

  • FRNC version in compliance with
    IEC 60332-1 and IEC 60754-1 & -2
    type designation  H07BQ-F  FRNC
  • other core configurations, cross
    sections and jacket colours
    manufactured upon request

 

 

Last Updated (Wednesday, 10 November 2010 15:31)