PVC Control Cables
oil resistant

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound TI2 with enhanced properties
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable) extruded dummy element
C no straight centre conductor allowed
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Inner jacket PVC compound TM2
F Screen tinned copper braid, coverage approx. 85%
G Jacket oil resistant PVC compound type TM5
G Colour grey RAL 7001

H05VV5-F

H05VV5-F [GCE Cables - Italy]

Technical Data

Conductor resistance R IEC 60228 class 5
Insulation resistance RI > 20 MOhm x km
Nominal voltage U0/U 300/500 V
Test voltage UT 3000 V
Bending radius rmin.
mobile application 12 x cable diameter
fixed installation 4 x cable diameter
Max. admissible conductor temperature
continuous +   70 °C
in case of short circuit + 150 °C
Temperature range
mobile application -   5 °C up to + 70 °C
fixed installation - 40 °C up to + 70 °C
Oil resistance HD 505.2.1 part 10, VDE 0472 part 803 class B
Flame retardance IEC 60332-1, EN 50265-2-1

 

Last Updated (Thursday, 04 November 2010 15:53)