H05VVC4V5-K UL/CSA
PVC Control Cables
oil resistant
Construction
A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable), no straight centre conductor allowed
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Inner jacket PVC compound type TM2
F Screen tinned copper braid, coverage approx. 85%
G Jacket oil resistant PVC compound type TM5
G Colour grey RAL 7001
H05VVC4V5-K UL/CSA
![H05VVC4V5-K UL/CSA [GCE Cables - Italy]](/images/stories/cables/Control_and_Power_Cables/H05VVC4V5-K_UL-CSA.jpg)
Technical Data
Conductor resistance R 0,50 mm2 < 39,0 Ohm/km
0,75 mm2 < 26,0 Ohm/km
1,00 mm2 < 19,5 Ohm/km
1,50 mm2 < 13,3 Ohm/km
2,50 mm2 < 7,98 Ohm/km
Insulation resistance RI > 20 MOhm x km
Transfer impedance ZT < 250 mOhm/m
Nominal voltage U0/U 300/500 V as per HAR
U 600 V as per UL/CSA
Test voltage UT 3000 V
Bending radius rmin.
mobile application 15 x cable diameter
fixed installation 6 x cable diameter
Max. admissible conductor temperature
continuous + 70 °C
in case of short circuit + 150 °C
Temperature range
mobile application - 15 °C up to + 70 °C as per HAR
up to + 90 °C as per UL/CSA
fixed installation - 40 °C up to + 70 °C as per HAR
up to + 90 °C as per UL/CSA
Oil resistance HD 505.2.1 part 10, VDE 0472 part 803
class B, UL 1581 part 50.182
Flame retardance IEC 60332-1, EN 50265-2-1,
UL VW1, CSA FT1
Options
- other core configurations, cross
sections and jacket colours
manufactured upon request - larger cross sections can be supplied
only with UL/CSA approval as they are
not included in HD 21.13 S1
Last Updated (Friday, 05 November 2010 15:51)