PVC Control Cables
oil resistant

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable), no straight centre conductor allowed
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Inner jacket PVC compound type TM2
F Screen tinned copper braid, coverage approx. 85%
G Jacket oil resistant PVC compound type TM5
G Colour grey RAL 7001

H05VVC4V5-K  UL/CSA

H05VVC4V5-K UL/CSA [GCE Cables - Italy]

Technical Data

Conductor resistance               R       0,50 mm2 < 39,0   Ohm/km
                                                       0,75 mm2 < 26,0   Ohm/km
                                                       1,00 mm2 < 19,5   Ohm/km
                                                       1,50 mm2 < 13,3   Ohm/km
                                                       2,50 mm2 <   7,98 Ohm/km
Insulation resistance               RI       > 20 MOhm x km
Transfer impedance                 ZT      < 250 mOhm/m
Nominal voltage                      U0/U   300/500 V as per HAR
                                             U        600 V as per UL/CSA
Test voltage                            UT      3000 V

Bending radius                        rmin.
       mobile application                      15 x cable diameter
       fixed installation                         6 x cable diameter

Max. admissible conductor temperature
       continuous                                +   70 °C
       in case of short circuit                + 150 °C

Temperature range
       mobile application                      - 15 °C up to + 70 °C  as per HAR
                                                                  up to + 90 °C  as per UL/CSA
       fixed installation                         - 40 °C up to + 70 °C  as per HAR
                                                                  up to + 90 °C  as per UL/CSA

Oil resistance                                   HD 505.2.1 part 10, VDE 0472 part 803
                                                       class B, UL 1581 part 50.182

Flame retardance                              IEC 60332-1, EN 50265-2-1,
                                                       UL VW1, CSA FT1

Options

  • other core configurations, cross
    sections and jacket colours
    manufactured upon request
  • larger cross sections can be supplied
    only with UL/CSA approval as they are
    not included in HD 21.13 S1

 

Last Updated (Friday, 05 November 2010 15:51)