LSZH Control Cables

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation LSZH compound type HI2 as per DIN VDE 0207 part 23
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable) extruded dummy element or flexible rope
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Jacket LSZH compound type HM2 as per DIN VDE 0207 part 24
E Colour grey RAL 7001

HSLH-..Z

HSLH-..Z [GCE Cables - Italy]

Technical Data

Conductor resistance             R         0,50 mm2 < 39,0   Ohm/km
                                                       0,75 mm2 < 26,0   Ohm/km
                                                       1,00 mm2 < 19,5   Ohm/km
                                                       1,50 mm2 < 13,3   Ohm/km
                                                       2,50 mm2 < 7,98   Ohm/km
                                                       4,00 mm2 < 4,95   Ohm/km
                                                       6,00 mm2 < 3,30   Ohm/km
                                                     10,00 mm2 < 1,91   Ohm/km
                                                     16,00 mm2 < 1,21   Ohm/km
                                                     25,00 mm2 < 0,780 Ohm/km
                                                     35,00 mm2 < 0,554 Ohm/km
                                                     50,00 mm2 < 0,386 Ohm/km
Insulation resistance              RI      > 20 MOhm x km
Nominal voltage                     U0/U  300/500 V
Test voltage                          UT      3000 V

Bending radius                      rmin.
       mobile application                    15 x cable diameter
       fixed installation                        4 x cable diameter

Temperature range
        mobile application                   - 15 °C up to + 70 °C
        fixed installation                      - 40 °C up to + 70 °C

Flame retardance                            IEC 60332-1, EN 50265-2-1
Fire retardance                                IEC 60332-3C, HD 405.3
Halogen content                              IEC 60754-1, EN 50267-2-1
Corrosivity                                      IEC 60754-2, EN 50267-2-2
Toxicity index                                 NES 713
Smoke density                               IEC 61034, EN 50268-2 LT > 60%
Chlorine content                             IEC 60754.1                      
PH and conductivity                        IEC 60754.2
Hydrolysis resistant        

Options

  • versions for use within an extended
    temperature range
    -15 °C up to + 90 °C (flexible)
    type designation  HSLHw-..Z
    -30 °C up to + 70 °C (flexible)
    type designation  HSLHk-..Z
  • oil resistant version
    as per IEC 60811-2-1
    type designation  HSLHö-..Z
  • low capacitance version in compliance
    with IEC 60332-1 (but not IEC 60332-3C)
    type designation  2YSLH-..Z
  • other core configurations, cross
    sections and jacket colours
    manufactured upon request

 

Last Updated (Monday, 08 November 2010 14:53)