HSLHCH-..Z
LSZH Control Cables
Construction
A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation LSZH compound type HI2 as per DIN VDE 0207 part 23
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable) extruded dummy element or flexible rope
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Inner jacket LSZH compound HM2 as per DIN VDE 0207 part 24
F Screen tinned copper braid, coverage approx. 82%
G Jacket LSZH compound HM2 as per DIN VDE 0207 part 24
G Colour grey RAL 7001
HSLHCH-..Z
![HSLHCH-..Z [GCE Cables - Italy]](/images/stories/cables/Control_and_Power_Cables/HSLHCH-..Z.jpg)
Technical Data
Conductor resistance R 0,50 mm2 < 39,0 Ohm/km
0,75 mm2 < 26,0 Ohm/km
1,00 mm2 < 19,5 Ohm/km
1,50 mm2 < 13,3 Ohm/km
2,50 mm2 < 7,98 Ohm/km
4,00 mm2 < 4,95 Ohm/km
6,00 mm2 < 3,30 Ohm/km
10,00 mm2 < 1,91 Ohm/km
16,00 mm2 < 1,21 Ohm/km
Insulation resistance RI > 20 MOhm x km
Transfer impedance ZT < 250 mOhm/m
Nominal voltage U0/U 300/500 V
Test voltage UT 3000 V
Bending radius r min.
mobile application 20 x cable diameter
fixed installation 6 x cable diameter
Temperature range
mobile application - 15 °C up to + 70 °C
fixed installation - 40 °C up to + 70 °C
Flame retardance IEC 60332-1, EN 50265-2-1
Fire retardance IEC 60332-3C, HD 405.3
Halogen content IEC 60754-1, EN 50267-2-1
Corrosivity IEC 60754-2, EN 50267-2-2
Toxicity index NES 713
Smoke density IEC 61034, EN 50268-2 LT > 60%
Chlorine content IEC 60754.1
PH and conductivity IEC 60754.1
Hydrolysis resistant
Options
- + 90 °C version HSLHCHw-..Z
- - 30 °C version HSLHCHk-..Z
- oil resistant version HSLHCHö-..Z
- low capacitance version in compliance
with IEC 60332-1 (but not IEC 60332-3C)
type designation 2YSLHCH-..Z - other core configurations, cross
sections and jacket colours
manufactured upon request
Last Updated (Monday, 08 November 2010 14:52)