S05Z1Z1-F
LSZH Power Cables
Construction
A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation LSZH compound type TI6
B Identification colour coded as per HD 308 S2
C Central filler (where applicable) extruded dummy element
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Jacket LSZH compound type TM7
E Colour grey RAL 7001
S05Z1Z1-F
Technical Data
Conductor resistance R 0,75 mm2 < 26,0 Ohm/km
1,00 mm2 < 19,5 Ohm/km
1,50 mm2 < 13,3 Ohm/km
2,50 mm2 < 7,98 Ohm/km
4,00 mm2 < 4,95 Ohm/km
Insulation resistance RI > 20 MOhm x km
Nominal voltage U0/U 300/500 V
Operating voltage UB0/UB 330/550 V AC
495/825 V DC
Test voltage UT 2500 V
Bending radius r min.
mobile application 7,5 x cable diameter
fixed installation 4 x cable diameter
Max. admissible conductor temperature
continuous + 60 °C
in case of short circuit + 150 °C
Temperature range
mobile application - 5 °C up to + 70 °C
fixed installation - 40 °C up to + 70 °C
Ozone resistance HD 21.2
Flame retardance IEC 60332-1, EN 50265-2-1
Fire retardance IEC 60332-3C, HD 405.3
Halogen content IEC 60754-1, EN 50267-2-1
Corrosivity IEC 60754-2, EN 50267-2-2
Toxicity index NES 713
Smoke density IEC 61034, EN 50268-2 LT > 60%
Options
- other core configurations, cross
sections and jacket colours
manufactured upon request
Last Updated (Monday, 08 November 2010 15:13)