PUR Control and Power Cables

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2 with enhanced properties
B Identification black number coded, green/yellow in the outer layer (JZ)
C Central filler (where applicable) extruded dummy element or flexible rope
C Cabling conductors cabled in concentric layers
D Separator non hygroscopic talcum powder
E Jacket polyurethane, shiny finish
E Colour grey RAL 7001

YSL11Y-..Z

Technical Data

Conductor resistance                  R                 0,50 mm2 < 39,0   Ohm/km
                                                                    0,75 mm2 < 26,0   Ohm/km
                                                                    1,00 mm2 < 19,5   Ohm/km
                                                                    1,50 mm2 < 13,3   Ohm/km
                                                                    2,50 mm2 < 7,98   Ohm/km
                                                                    4,00 mm2 < 4,95   Ohm/km
                                                                    6,00 mm2 < 3,30   Ohm/km
                                                                  10,00 mm2 < 1,91   Ohm/km
                                                                  16,00 mm2 < 1,21   Ohm/km
                                                                  25,00 mm2 < 0,780 Ohm/km
                                                                  35,00 mm2 < 0,554 Ohm/km
                                                                  50,00 mm2 < 0,386 Ohm/km
Insulation resistance                   RI              > 20 MOhm x km
Nominal voltage                          U0/U         300/500 V
Test voltage                                UT            3000 V

Bending radius                            r min.
        mobile application                               12 x cable diameter
        fixed installation                                  4 x cable diameter

Temperature range
        mobile application             -  5 °C up to + 80 °C
        fixed installation               - 40 °C up to + 80 °C

Oil resistance                          HD 505.2.1, VDE 0472 part 803 class A/B
Hydrolysis resistance               HD 22.10
Ozone resistance                     HD 22.2

Options

  • UL/CSA versions
    300 V  80 °C (slimline)
    for cross sections up to 1,50 mm2
    600 V  80 °C (larger diameters)
    for the whole range
  • low adhesion jacket with matte finish
  • additional polyester fleece taping over
    the screen
  • flame retardant as per IEC 60332-1
  • FRNC version in compliance with
    IEC 60332-1 and IEC 60754-1 & -2
    type  TPESL11Y-..Z  FRNC
  • other core configurations, cross
    sections and jacket colours
    manufactured upon request

                                                                      

Last Updated (Monday, 08 November 2010 16:10)