LSZH Electronics Cables

Construction

A Conductor flexible bare copper as per VDE 0812 resp. IEC 60228 class 5
B Insulation PE compound type 2Y as per DIN VDE 0207 part 23
B Identification colour code as per DIN 47100 (with repetition of colours as of the 45th core)
C Central filler (where applicable) extruded dummy element or flexible synthetic rope
C Cabling conductors cabled in concentric layers
D Taping polyester foil
E Screen tinned copper braid, coverage approx. 82%
F Jacket LSZH compound type TM7 as per DIN VDE 0281 part 24
F Colour grey RAL 7001

Li2YCH DIN

Li2YCH DIN [GCE Cables - Italy]

Technical Data

Conductor resistance    R        0,14 mm2 < 138,0 Ohm/km
                                             0,25 mm2 <   77,5 Ohm/km
                                             0,34 mm2 <   56,0 Ohm/km
                                             0,50 mm2 <   39,0 Ohm/km
                                             0,75 mm2 <   26,0 Ohm/km
Insulation resistance     RI       >  20 MOhm x km
Operating capacitance   C       0,14 mm2 <   90 pF/m
                                             0,25 mm2 < 100 pF/m
                                             0,34 mm2 < 110 pF/m
                                             0,50 mm2 < 120 pF/m
                                             0,75 mm2 < 120 pF/m
Transfer impedance      ZT        <   250 mOhm/m
Operating voltage         UB      350 V (peak) 0,14 mm2
                                             500 V (peak) 0,25 mm2 & 0,34 mm2
                                 U0/U    300/500 V as of 0,50 mm2
Test voltage                UT       800 V 0,14 mm2
                                            1200 V 0,25 mm2 & 0,34 mm2
                                            3000 V as of 0,50 mm2
Bending radius rmin.
            mobile application     12 x cable diameter
            fixed installation        6 x cable diameter
Temperature range
           mobile application      - 15 °C up to + 70 °C
           fixed installation         - 40 °C up to + 70 °C
Flame retardance                  IEC 60332-1, EN 50265-2-1
Halogen content                    IEC 60754-1, EN 50267-2-1
Corrosivity                            IEC 60754-2, EN 50267-2-2
Toxicity index                       NES 713
Smoke density                     IEC 61034, EN 50268-2 LT > 60%

 

Last Updated (Tuesday, 09 November 2010 15:08)