LifYCY UL DIN
PVC Trailing Cables
Construction
A Conductor highly flexible bare copper as per IEC 60228 class 6
B Insulation semi-rigid PVC
B Identification colour code as per DIN 47100
C Central filler (where applicable), no straight centre conductor allowed
C Cabling conductors cabled in concentric layers
C lateral fillers admitted
D Taping polyester fleece
E Screen tinned copper braid, coverage approx. 85%
F Jacket special PVC compound type as per class 43
F Colour grey RAL 7001
LifYCY UL DIN
![LifYCY UL DIN - [GCE Cables - Italy]](/images/stories/cables/Trailing_Cables_for_Cable_Chains/LIfYCY_UL_DIN.jpg)
Technical Data
Conductor resistance R 0,14 mm2 < 138,0 Ohm/km
0,25 mm2 < 77,5 Ohm/km
0,34 mm2 < 56,0 Ohm/km
Insulation resistance RI > 200 MOhm x km
Operating capacitance C 0,14 mm2 < 90 pF/m
0,25 mm2 < 100 pF/m
0,34 mm2 < 110 pF/m
Operating voltage UB 300 V
Test voltage UT 1500 V
Bending radius rmin. 12 x cable diameter
Travelling speed vmax.
freely moving 4 m/s 4 m/s
sliding 2 m/s 2 m/s
Acceleration amax. 2 m/s2 4 m/s2
Bending cycles at a travelling distance of 7 m
2 mio. 1 mio.
Temperature range
mobile application - 5 °C up to + 80 °C
fixed installation - 40 °C up to + 80 °C
Oil resistance IEC 60811-2-1
Flame retardance IEC 60332-1, EN 50265-2-1
Options
- other core configurations and cross
sections manufactured upon request - black outer jacket
type designation
LifYCY UL DIN BK
Last Updated (Monday, 21 March 2011 16:25)