PVC Installation Cables
for Siemens® controls

Construction

A Conductor tinned copper, concentrically stranded
A 0,18 mm2 7 x 0,180 mm
A 0,22 mm2 7 x 0,203 mm
B Insulation PVC compound type TI3
B Identification special colour code, refer to the CAD drawing for our standard
C Cabling conductors twisted to pairs
D Cabling conductors resp. pairs cabled in concentric layers
E Taping polyester fleece
F Screen tinned copper braid, coverage approx. 85%
G Jacket PVC compound type TM2 with enhanced properties
G Colour grey RAL 7000

LivYCY  SI

LivYCY SI - [GCE Cables - Italy]

LivYCY SI - [GCE Cables - Italy]

LivYCY SI - [GCE Cables - Italy]

Technical Data

Conductor resistance                         R                0,18 mm2 < 105,0 Ohm/km
                                                                          0,22 mm2 <   97,0 Ohm/km
Insulation resistance                          RI               > 200 MOhm x km
Operating capacitance                       C                0,18 mm2 <   95 pF/m
                                                                          0,22 mm2 < 100 pF/m
Operating voltage                              UB              300 V
Test voltage                                      UT              1500 V

Bending radius                                  rmin.           10 x cable diameter

Temperature range
        mobile application                    -   5 °C up to + 80 °C
        fixed installation                       - 40 °C up to + 80 °C

Oil resistance                                  IEC 60811-2-1

Flame retardance                             IEC 60332-1, EN 50265-2-1

Options

  • tinned copper drain wire
  • PUR trailing cables
  • PUR trailing cables low capacitance versions