PVC Power Cables

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2 with enhanced properties
B Identification black number coded, green/yellow in the outer layer
C Central filler (where applicable) extruded dummy element
C Cabling conductors cabled in a concentric layer
D Separator non hygroscopic talcum powder
E Jacket PVC compound type TM2 with enhanced properties
E Colour black RAL 9005

YSLY-JZ 0,6/1 kV

YSLY-JZ 0.6/1 KV - [GCE Cables - Italy]

Technical Data

Conductor resistance                            R                  1,50 mm2 < 13,30   Ohm/km
                                                                               2,50 mm2 <   7,98   Ohm/km
                                                                               4,00 mm2 <   4,95   Ohm/km
                                                                               6,00 mm2 <   3,30   Ohm/km
                                                                             10,00 mm2 <   1,91   Ohm/km
                                                                             16,00 mm2 <   1,21   Ohm/km
                                                                             25,00 mm2 <   0,780 Ohm/km
                                                                             35,00 mm2 <   0,554 Ohm/km
                                                                             50,00 mm2 <   0,386 Ohm/km
Insulation resistance                             RI               > 20 MOhm x km
Nominal voltage                                   U0/U            0,6/1 kV
Operating voltage                                 UB0/UB       0,7/1,2 kV AC
                                                                             0,9/1,8 kV DC
Peak voltage                                        Û                1,7 kV
Test voltage                                         UT               4 kV

Bending radius                                     rmin.
       mobile application                                           15 x cable diameter
       fixed installation                                               8 x cable diameter

Max. admissible conductor temperature
       continuous                                                      +   80 °C
       in case of short circuit                                      + 160 °C

Temperature range
        mobile application                        -   5 °C up to + 80 °C
        fixed installation                           - 40 °C up to + 80 °C

Oil resistance                                      IEC 60811-2-1
Flame retardance                                 IEC 60332-1, EN 50265-2-1

Options

  • other core configurations and cross
    sections manufactured upon request
  • FRNC version  HSLH-JZ 0,6/1 kV
    fire retardant as per IEC 60332-3C
    non corrosive as per IEC 60754-1 & -2
  • PUR versions