Construction
A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound TI2 with enhanced properties
B Identification black number coded, green/yellow
C Central filler extruded dummy element
C Cabling conductors cabled in a concentric layer
D Separator non hygroscopic talcum powder
E Inner jacket PVC compound TM2 with enhanced properties
F Screen tinned copper braid, coverage approx. 85%
G Jacket PVC compound TM2 with enhanced properties
G Colour orange RAL 2003
YSLYCY-JZ
![YSLYCY-JZ - [GCE Cables -Italy]](/images/stories/cables/Special_Cables_for_Factory_Automation/YSLYCY-JZ.jpg)
Technical Data
Conductor resistance R 1,50 mm2 < 13,30 Ohm/km
2,50 mm2 < 7,98 Ohm/km
4,00 mm2 < 4,95 Ohm/km
6,00 mm2 < 3,30 Ohm/km
10,00 mm2 < 1,91 Ohm/km
16,00 mm2 < 1,21 Ohm/km
25,00 mm2 < 0,780 Ohm/km
35,00 mm2 < 0,554 Ohm/km
50,00 mm2 < 0,386 Ohm/km
Insulation resistance RI > 20 MOhm x km
Transfer impedance ZT < 250 mOhm/m
Nominal voltage U0/U 0,6/1 kV
Operating voltage UB0/UB 0,7/1,2 kV AC
0,9/1,8 kV DC
Peak voltage Û 1,7 kV
Test voltage UT 4 kV
Bending radius rmin.
mobile application 15 x cable diameter
fixed installation 8 x cable diameter
Max. admissible conductor temperature
continuous + 80 °C
in case of short circuit + 160 °C
Temperature range
mobile application - 5 °C up to + 80 °C
fixed installation - 40 °C up to + 80 °C
Oil resistance IEC 60811-2-1
Flame retardance IEC 60332-1, EN 50265-2-1
Options
- other core configurations and cross
sections manufactured upon request - FRNC version HSLHCH-JZ 0,6/1 kV
fire retardant as per IEC 60332-3C
non corrosive as per IEC 60754-1 & -2