PUR Power Cables

Construction

A Conductor flexible bare copper as per IEC 60228 class 5
B Insulation PVC compound type TI2 with enhanced properties
B Identification black number coded, green/yellow in the outer layer
C Central filler (where applicable) extruded dummy element
C Cabling conductors cabled in a concentric layer
C lateral fillers admitted
D Taping polyester fleece
E Jacket polyurethane, matte finish
E Colour black RAL 9005

YSL11Y-JZ 0,6/1 kV

YSL11Y-JZ 0.6/1 KV - [GCE Cables -Italy]

Technical Data

Conductor resistance                                R               1,50 mm2 < 13,30   Ohm/km
                                                                                2,50 mm2 <   7,98   Ohm/km
                                                                                4,00 mm2 <   4,95   Ohm/km
                                                                                6,00 mm2 <   3,30   Ohm/km
                                                                              10,00 mm2 <   1,91   Ohm/km
                                                                              16,00 mm2 <   1,21   Ohm/km
                                                                              25,00 mm2 <   0,780 Ohm/km
                                                                              35,00 mm2 <   0,554 Ohm/km
                                                                              50,00 mm2 <   0,386 Ohm/km
Insulation resistance                                RI             > 20 MOhm x km
Nominal voltage                                       U0/U         0,6/1 kV
Operating voltage                                    UB0/UB     0,7/1,2 kV AC
                                                                              0,9/1,8 kV DC
Peak voltage                                           Û              1,7 kV
Test voltage                                            UT             4 kV

Bending radius                                       rmin.
       mobile application                                            15 x cable diameter
       fixed installation                                                8 x cable diameter

Max. admissible conductor temperature
       continuous                                    +   80 °C
       in case of short circuit                    + 160 °C

Temperature range
       mobile application                          -   5 °C up to + 80 °C
       fixed installation                             - 40 °C up to + 80 °C

Oil resistance                                      HD 505.2.1, VDE 0472 part 803 class A/B
Hydrolysis resistance                           HD 22.10
Ozone resistance                                 HD 22.2

Options

  • other core configurations and cross
    sections manufactured upon request
  • FRNC version  2YSL11Y-JZ 0,6/1 kV
    flame retardant as per IEC 60332-1
    non corrosive as per IEC 60754-1 & -2
  • PVC versions

 